112 en | MAC - Main Access Controller BIS 2.3 - Access Engine
F.01U.028.713 | V 2.3.0.1 | 2009.11 Installation manual Bosch Sicherheitssysteme GmbH
then the MAC will be restarted. Not until the MAC has been
shut down completely will its corresponding service be
terminated.
2. Terminating the service "AUTO_MAC".
With this option the safety check and termination message are
not displayed.
1. Shutting down the Master ProcessControl.
All dependent processes will be stopped before the master
finally terminates itself. The safety check does not appear
in this case, but the restart message does. Even when the
MAC has been terminated the service remains in status
"started". Hence the service must be terminated and
restarted in order to restart the MAC.
11.3.3 Warm start
Along with the shutdown option ProcessControl provides a
means of restarting individual processes:
A restart of the master proceeds similarly to shutdown scenario
3 above; i.e. if one requires a restart then the restart query
should be affirmed or left unsanswered. Warm start then
reinitilizes the individual processes. With the exception of
MESSENGER and SYSTEM all other MAC processes can also be
restarted. The restart is initiated automatically after shutdown
without further user intervention.
11.3.4 Cold start
Cold, as opposed to warm, start means that all essential system
data should be requested and loaded from the DMS. To do this
it is necessary to delete the data already loaded thus forcing
the MAC to request all data at startup.
Shut down the MAC and then delete all files with the extensions
.dat and idx in the MAC’s DB directory. Do not delete the
folders PROTO and SAVE). Then restart the MAC.