BIS 2.3 - Access Engine Upgrade | en 15
Bosch Sicherheitssysteme GmbH Installation manual F.01U.028.713 | V 2.3.0.1 | 2009.11
All configuration and access control data are preserved.
Upon starting the BIS Configuration browser and loading your
configuration the access Engine database will have to be
synchronized. Affirm the synchronization dialog in order to use
your accustomed data and settings.
2.3 Updating Controller (LAC) Software
The software upgrade installs new programs which enable LACs
to make use of new functionality usable in access control.
In order for the controllers to use the new software they may
first need a firmware upgrade (Bootloader), therefore in order
to prevent the controllers from automatically downloading the
software from the MAC prematurely all configured LACs are set
offline by the upgrade process. Hence they initially have no
connection with the MAC.
In the device editor on the first page/tab of the LACs you can
view the de-/activation of the MAC-connection.
NOTICE!
The controllers continue to work with the same settings, in
order to ensure as smooth a transition as possible.