BIS 2.3 - Access Engine Setting up additional workstations | en 39
Bosch Sicherheitssysteme GmbH Installation manual F.01U.028.713 | V 2.3.0.1 | 2009.11
Readers with serial interface
Dialog readers are generally special readers with an RS232
interface meaning they can be connected to any workstation as
follows:
Connect the dialog reader to a free COM port on the
workstation using an RS232 cable.
For readers with their own address setting, set the reader
address to "1".
Readers with USB interface
1. Start the Configuration Browser as described in
Section 4.1 Starting the Configuration Browser, Page 24.
2. In the Infrastructure menu switch to the ACE dialog
reader dialog.
from the left-hand list select the workstation to which
the dialog reader has been connected .
Select the connected reader type in the Reader type
list field.
Change the default entry in the COM port field
according to the selected interface.
If necessary, change the default parameters according
to the manufacturer's instructions for the dialog
reader.
in order to use the card reader to capture and search for
personnel data you will need to change the default setting from
manual input. In Access Engine > Personnel Data > Persons
click the u button to the right Reader button and select the
i
NOTICE!
If you can not see the workstation in this list field, first create
the workstation as described in Section 5.1.2 Setting up the
Configuration Browser.
i
NOTICE!
You can reset parameter definitions back to the default values
at any time by clicking the Default values button.