80 en | DMS - Data Management System BIS 2.3 - Access Engine
F.01U.028.713 | V 2.3.0.1 | 2009.11 Installation manual Bosch Sicherheitssysteme GmbH
The processes are started in the sequence in which they appear
in the process description, except for the batch processes.
type Process type:
BASE: Base Process - the process is
essential. If such a process fails then
the BIS system as a whole will crash.
NORMAL: the process is not treated
in a special manner. Failed processes
of this type are typically restarted by
their parents.
BATCH: The process is a batch
process that is started at a particular
time.
ready Indicates whether the master has to
wait until the process has sent the
message that it is ready.
0: master does not have to wait.
1: master has to wait for the ready
message.
batchStart Start time of the batch processes
batchPeriod Describes how the processes are
started periodically at different
times: DAILY: has to be started daily.
WEEKLY: has to be started weekly.
errorReset Time after which the error counter is
reset (in hours).
exitNumber Describes the process order for
shutting down the system.
restartLimit - maximum number of
restarts permitted. In case of a
process failure, a restart counter is
set up and the process is restarted. If
the restart counter exceeds the
restart limit, the process is no longer
restarted.
Named Parameter Description
Table 10.1 Block entries in the process description file