Solution 6000-IP
30
Bosch Security Systems 10/22 BLCC615R
Quick Start Guide
Inputs > Zone Properties >
Pulse Count
MENU 3-1-3
Pulses 0 0
00 - No Pulse Count 08 - 8 Inertia Pulses
01 - 1 Pulse 09 - 9 Inertia Pulses
02 - 2 Pulses 10 - 10 Inertia Pulses
03 - 3 Pulses 11 - 11 Inertia Pulses
04 - 4 Pulses 12 - 12 Inertia Pulses
05 - 5 Pulses 13 - Door Open Too Long
06 - 6 Inertia Pulses 14 - PreDelay
07 - 7 Inertia Pulses 15 - Reserved
Enter 0 – 15 + [OK] to program the number of pulses the
zone must register within the zone pulse count time.
Inputs > Zone Properties >
Pulse Count Time
MENU 3-1-4
Seconds
1 2 0
Enter value between 000 – 255 then select muliplier of
seconds, minutes or hours. Press [OK] to save. Use the
[←] and [→] keys to toggle between value and multiplier
settings.
Inputs > Zone Properties >
Door Assignment
MENU 3-1-5
0 0
00 - Disabled
01 - Door 1 Name 09 - Door 9 Name
02 - Door 2 Name 10 - Door 10 Name
03 - Door 3 Name 11 - Door 11 Name
04 - Door 4 Name 12 - Door 12 Name
05 - Door 5 Name 13 - Door 13 Name
06 - Door 6 Name 14 - Door 14 Name
07 - Door 7 Name 15 - Door 15 Name
08 - Door 8 Name 16 - Door 16 Name
A single door can be assigned to each zone. Use the []
and [] keys to highlightdoor name, then press [OK] to
save.
Inputs > Zone Properties >
Report Route
MENU 3-1-6
00 - Log Events Only 0 1
01 - Dest 1 + Log
02 - Dest 2 + Log
03 - Dest 1 & 2 + Log
04 - Dest 2 If 1 Fails
Use [] and [] keys or enter 0 - 4 + [OK] to set the
destination zone reports are sent to.
Zone Assignments
Zone Assignment Table
Module
Number
Address Setting
Zone Numbers
(Single EOL)
Zone Numbers
(Alarm+Tamper EOL)
Zone
Numbers
(Split EOL)
Single or Alarm +
Tamper EOL With CM705B
+ CM707B Module
SW1 SW2 SW3 SW4 SW5
Control Panel 1 to 8 1 to 8 1 to 16 1 to 8
1 = OFF OFF OFF OFF OFF 17 to 24 17 to 24 17 to 32
17 to 24
25 to 32 on the CM707B
2 = ON OFF OFF OFF OFF 33 to 40 33 to 40 33 to 48
33 to 40
41 to 48 on the CM707B
3 = OFF ON OFF OFF OFF 49 to 56 49 to 56 49 to 64
49 to 56
57 to 64 on the CM707B
4 = ON ON OFF OFF OFF 65 to 72 65 to 72 65 to 80
65 to 72
73 to 80 on the CM707B
5 = OFF OFF ON OFF OFF 81 to 88 81 to 88 81 to 96
81 to 88
89 to 96 on the CM707B
6 = ON OFF ON OFF OFF 97 to 104 97 to 104 97 to 112
97 to 104
105 to 112 on the CM707B
7 = OFF ON ON OFF OFF 113 to 120 113 to 120 113 to 128
113 to 120
121 to 128 on the CM707B
8 = ON ON ON OFF OFF 129 to 136 129 to 136 129 to 144
129 to 136
137 to 144 on the CM707B
Table 16: Zone Assignments