35
Bosch Security Systems 10/22 BLCC615R
Solution 6000-IP
Quick Start Guide
Output Assignments
Output Assignments
Module
Number
Address Setting
Output
Number
SW1 SW2 SW3 SW4 SW5
Control Panel 1 to 5
Virtual Outputs 6 to 8
1 = OFF OFF OFF OFF OFF 9 to 12
2 = ON OFF OFF OFF OFF 13 to 16
3 = OFF ON OFF OFF OFF 17 to 20
4 = ON ON OFF OFF OFF 21 to 24
5 = OFF OFF ON OFF OFF 25 to 28
6 = ON OFF ON OFF OFF 29 to 32
7 = OFF ON ON OFF OFF 33 to 36
8 = ON ON ON OFF OFF 37 to 40
Table 20: Address Configuration and Output Assignments
Outputs > Properties >
Event Assignment
MENU 4-1-2
0 0 0
(A) =
Area Assignment
Assign to Area 1 to 8 (0 = Any Area)
(P) =
Control Panel
(Op) =
Output Assignment
Assign to Output 1 to 40 (0 = Any Output)
(Zn) =
Zone Assignment
Assign to Zone 1 to 144 (0 = Any Zone)
(Ur) =
User Assignment
Assign to User 1 to 255 (0 = Any User)
(Tz) =
TimeZone Assignment
Assign to TimeZone 1 to 16 (0 = Any TimeZone)
(Dr) =
Door Assignment
Assign to Door Assignment 1 to 16 (0 = Any Door)
(Kp) =
Keypad Assignment
Assign to Keypad/LAN Reader 1 to 16 (0 = Any
Keypad/LAN Reader)
(Rr) =
Reporting Destination
Assign to Destination 1 or 2 (0 = Destination 1 and/
or Destination 2)
(Ma) =
Macro Group Assignment
Assign to Macro Group (0 = Any Macro Group)
(CLI) =
CLI Trigger Table
Assign to CLI Trigger Table 1 or 2 (0 = Both Tables)
Use [] and [] keys to program which Area, User, Zone,
Keypad or Door Assignment etc you want the output to
follow then press [OK].
Outputs > Properties >
Output Polarity
MENU 4-1-3
0 0
00 - Open To Low 08 - Low To Open + Pre
01 - Open To Low + Pre 09 - Low Latching Open
02 - Open Latching Low 10 - Low Pulsing Open
03 - Open Pulsing Low 11 - Low 1 Shot Open
04 - Open 1 Shot Low 12 - 1 Shot Open+Retrigger
05 - 1 Shot Low+Retrigger 13 - 1 Shot Open + Reset
06 - 1 Shot Low + Reset 14 - Speaker Output
07 - Low To Open 15 - Toggle
Enter 0 – 15 + [OK] to program the output polarity type.
Each output can only have one polarity type programmed.
Outputs > Properties >
Time Parameter
MENU 4-1-4
0 0 0 0 0 0 0 0 0 0 0 0
Hour Minute Seconds 10
th
Sec
The time base parameter is only applicable for output types
that are programmed as one shot or pulsing. Program 0 to
255 for each of the units (Hour, Minute, Seconds and 10th
of a second) for the time parameter. Add the units together
to give the total one shot time or pulsing on/off time.
One Shot Mode
The time base is the length of time that the output will
operate.
For example, you may want a strobe output to operate
for 1 hour, Either of the examples below will achieve the 1
hour time.
Total Time Hour Minute Seconds 10th Sec
60 Minutes 001 000 000 000
60 Minutes 000 060 000 000
Table 21: One-Shot Polarity Example
Pulsing Mode
The time base is the unit of time that the output will pulse
on and off. If the time base is programmed for 60 seconds,
the output will pulse on for 60 seconds and then off for 60
seconds (repeat) until the output is reset.