Environmental Alarms
AC fail alarm
Alarm output
When the alarm occurs, the following message displays:
TID-000 01-09-10 08-15-00
** 001 REPT ALM ENV
"N2-1:MJ,POWER,NSA,9-10,8-15-00,NEND;"
Clearing output
You will see this message once the alarm has been cleared from the system.
TID-000 01-09-10 08-15-00
A 001 REPT EVT ENV
"N2-1:POWER,CL,9-10,8-15-00;"
Description Severity
The AC fail (POWER) alarm indicates that commercial power has
failed or is absent.
Calix outdoor cabinets are designed to provide eight hours of battery
backup. If the POWER alarm persist for longer than eight hours
service may be lost. Connect a backup power generator to the outdoor
cabinet to prolong the battery backup capabilities.
Major