ACTECH SMV VFD
Table 5 - Cross Reference Table
NOTE: To adjust the speed of 3 phase direct-drive motors, a variable frequency drive is required.
Figure 34 - Motor Wiring Diagrams
HP Part Number Volts
Input
Input
Input Amps 1Ø
120V AC
Input Amps 1Ø
240V AC
Output
Amps
Breaker 1Ø
120V AC
Breaker 1Ø
240V AC
1 ESV751N01SXB 120/240V X - 16.6 8.3 4.2 25 15
1.5 ESV112N01SXB 120/240V X - 20 10 6 30 20
HP Part Number Volts
Input
Input
Input Amps 1Ø Input Amps 3Ø
Output
Amps
Breaker 1Ø Breaker 3Ø
1 ESV751N02YXB 240V X X 8.8 5 4.2 15 15
1.5 ESV112N02YXB 240V X X 12 6.9 6 20 15
2 ESV152N02YXB 240V X X 13.3 8.1 7 25 15
3 ESV222N02YXB 240V X X 17.1 10.8 9.6 30 20
1 ESV751N04TXB 480V - X - 2.5 2.1 - 15
1.5 ESV112N04TXB 480V - X - 3.6 3 - 15
2 ESV152N04TXB 480V - X - 4.1 3.5 - 15
3 ESV222N04TXB 480V - X - 5.4 4.8 - 15
1 ESV751N06TXB 600V - X - 2 1.7 - 15
2 ESV152N06TXB 600V - X - 3.2 2.7 - 15
3 ESV222N06TXB 600V - X - 4.4 3.9 - 15
W2
W3
U2
U3
V2
V3
W2
W3
U2
U3
V2
V3
W4
U4
V4
U1
V1
W1
L1
L2
L3
2TB1
2TB2
NCC
2TP1
2TP2
PTC
2TB1
2TB2
NCC
2TP1
2TP2
PTC
W4
U4
V4
L1
L2
L3
U1
V1
W1
2TB1
2TB2
NCC
2TP1
2TP2
PTC
W4
U4
V4
U3
U1
V3
V1
W3
W1
L1
L2
L3
2TB1
2TB2
NCC
2TP1
2TP2
PTC
W2
U2
V2
W2
U2
V2
W4
U4
V4
U3
U1
V3
V1
W3
W1
L1
L2
L3
Connection Diagram
Tightening Torques for Screw Connections:
M4: 0.7-1.0Nm M5: 1.6-2.2Nm M6: 2.2-3.5Nm
M8: 6-8Nm M10: 10-14Nm M12: 14-20Nm
230V at 50Hz
265V at 60Hz
400V at 50Hz
460V at 60Hz
115V at 50Hz
132V at 60Hz
200V at 50Hz
230V at 60Hz

Table of Contents