ECPM03 Menu Tree
NOTE: Parameters marked with an (*) are not applicable to general ventilation fans.
CONFIGURATION
NUMBER OF FANS
SET TOTAL NUMBER OF
FANS (1-10)
DEFAULT = 1
NUMBER OF GROUPS
SET TOTAL NUMBER OF
GROUPS (1-10)
DEFAULT = 1
NUMBER OF HMIS
SET TOTAL NUMBER OF
HMIS (1-10)
DEFAULT = 1
BMS FAN SETTINGS
SET BMS FAN SPEED FOR
INDIVIDUAL FANS (ILA)
(15-55 HZ / 80 HZ)
FANS
FANS
DEFAULT = 15 HZ FOR ALL
ASSIGN FANS TO FAN
GROUPS
DEFAULT = FAN 1
ASSIGNED TO GROUP 1
NUMBER OF ROOM
SENSORS
SET TOTAL NUMBER OF
ROOM TEMP SENSORS
(0-32)
DEFAULT = 0
SENSORS
ASSIGN ROOM TEMP
ASSIGN ROOM TEMP
SENSORS TO FAN
GROUPS
DEFAULT = NO ROOM
TEMP SENSORS
ASSIGNED
SENSORS
ASSIGN HMI TEMP
ASSIGN HMI TEMP
SENSORS TO FAN
GROUPS
DEFAULT = HMI 1
ASSIGNED TO GROUP 1
TIMER SETTINGS
SET FAN GROUP TIMER
(AUTO/OFF/NONE)
AND TIME SETTING
(1-18 HOURS)
DEFAULT = ALL TIMERS
SET TO NONE
GROUP SETTINGS
ACTIVATION
TEMPERATURE
SET FAN GROUP ACTIVATION
TEMPERATURE
(40-100°F) (5.5-38°C)
DEFAULT = 75°F (25°C)
MODULATION BAND
SET FAN GROUP MODULATION
BAND (1-15°F) (0.5-7°C)
DEFAULT = 5°F (3°C)
HYSTERESIS
SET FAN GROUP HYSTERESIS
TEMPERATURE
(0.5-20°F) (0.5-11°C)
MINIMUM
DEFAULT = 1°F (0.5°C)
CYCLE TIME
SET FAN GROUP MINIMUM CYCLE
TIME (1 - 60 MINUTES)
DEFAULT = 30 MINUTES
MAXIMUM VFD
FREQUENCY
DEFAULT = 55 HZ (HVLS)
MINIMUM VFD
SET FAN GROUP MAXIMUM VFD
FREQUENCY
(MIN FREQUENCY - 55 HZ HVLS)
(MIN FREQUENCY - 80 HZ VENT)
DEFAULT = 80 HZ (VENT)
FREQUENCY
DEFAULT = 15 HZ
SET FAN GROUP MINIMUM VFD
FREQUENCY
(15 HZ - MAX FREQUENCY)
ALARM
HIGH TEMPERATURE
SET FAN GROUP HIGH
TEMPERATURE ALARM
(40-150°F) (5.5-65°C)
DEFAULT = 110°F (45°C)
ALARM
LOW TEMPERATURE
SET FAN GROUP LOW
TEMPERATURE ALARM
(40-100°F) (5-38°C)
DEFAULT = 50°F (10°C)
*REVERSE TEMP.
*REVERSE TEMPERATURE
SETTING RANGE
*DEFAULT = 55°F (13°C)
*REV. HYSTERESIS
*SET REVERSE HYSTERESIS
(0.5-20°F) (0.5-9.5°C)
*DEFAULT = 2°F (1°C)
*REV. VFD FREQ.
*DEFAULT = 15 HZ
*REVERSE VFD SETTING BETWEEN
LOW SPEED AND HIGH SPEED
SELECT
TEMPERATURE UNIT
SET DEGREES °F OR °C DEFAULT = DEGREES °F
FAN DIRECTION
SET INDIVIDUAL FAN
ROTATION (NO
REWIRING REQUIRED)
DEFAULT = FORWARD
FOR ALL FANS
SET HMI DIMMING
DIM HMI
(ON OR OFF)
DEFAULT = OFF
SET DIM DELAY TIME
DIM DELAY TIME
(10-300 SECONDS)
DEFAULT = 10 SECONDS
SYSTEM BYPASS SET SYSTEM BYPASS DEFAULT = OFF
SET MB ADDRESS
ADDRESS
SET CONTROL MODBUS
DEFAULT = 90
PRODUCT MODE HVLS OR VENT
DDC MODE
ENABLE OR DISABLE
DIRECT DIGITAL CONTROL DISABLED
DEFAULT = DDC
SCHEDULING
ENABLE OR DISABLE
SCHEDULING
DEFAULT = DISABLED
*REV. ACTIVATION
*ENABLE OR DISABLE
REV. ACTIVATION
*DEFAULT = DISABLED
SET SYSTEM TIME
SET YEAR (0-99)
YEAR
DEFAULT = CURRENT
EXAMPLE 15 = 2015
SET MONTH (1-12)
MONTH
DEFAULT = CURRENT
SET DAY (1-31)
DAY
DEFAULT = CURRENT
SET HOUR (0-23)
HOUR
DEFAULT = CURRENT
SET MINUTE (0-59)
MINUTE
DEFAULT = CURRENT
SET SECOND (0-59)
SECOND
DEFAULT = CURRENT