Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
67
T5x Override Duration
If using a T55, T56, or T59 sensor, this is the amount of time
that the controller runs in the occupied mode when a user presses the sensor's override
button for 1 to 10 seconds.
D:
R:
1 hr
0 to 24 hours
ZS Sensor Binder / ZS Zone Temp / ZS Zone Humidity / ZS Zone CO2
Ctrl+click
on the name of these properties to access the microblock popup
Properties
page >
Details
tab. See below for instructions on configuring your ZS Sensors.
See the microblock Help for more detailed explanations.
ZS Sensor Binder
- Use the
Associated Sensors
table to configure the Rnet to use
additional ZS Sensors.
Network Type
- Set to
Rnet
Address
- Enter the DIP switch settings that are on the additional ZS sensors (up to 5
total)
Lock Display
- Check to make the sensor display-only
D:
(Index)
- (1)
Network Type
- Rnet
Address
- 1
ZS Zone Temp
- Configure additional ZS temperature sensors used on the RTU Open.
Use
- Check to include ZS sensors' value in the
Combined Algorithm
(
Average
is the
default).
Raw Value
- Displays sensed temperature for each ZS temperature sensor's address
Calibration
- If needed, enter value to adjust the
Corrected Value
from the
Raw
Value
, in order to calibrate an individual ZS sensor's sensed value.
Combination Algorithm
- Use
Average
,
Maximum
, or
Minimum
ZS temperature to
calculate the
Corrected Value
for temperature control.
D:
(Index) Area
- (1) Main ZS
Sensor
Use -
checked
Calibration
- 0
Combination Algorithm
-
Average
Input Smoothing
-
Medium
Show on Sensors
-
Calculated Value
Display Resolution
- 1
COV Increment
- .1