31  FAILED TO START - AUTO MODE 
  TRIGGER-ON: Engine has tried to start three times unsuccessfully in the auto start mode. 
  UNIT CONTROL: Unit Shutdown & Alarm 
  RESET CONDITION: Alarm may be manually reset via keypad or by turning the unit off, then back on 
again. 
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the 
alarm(s). (Refer to Note 1 Page 7-1) Operate the unit through the appropriate modes to see if any active alarm 
occurs. Continue with the steps below as necessary. 
Check Fuel Level in Tank. 
a. Check fuel gauge on tank. 
a. Check for the following alarms: 
130 Check engine RPM sensor 
71 Check for Bad F2 or F3 Fuse 
40 Check Glow Plugs 
35 Check Starter Circuit. 
Alarm conditions must be corrected and the alarm 
cleared to continue. 
c. Inspect solenoid & connector pins 
& terminals 
No damage to solenoid 
No damaged or corroded pins 
d. Check voltage at the fuel solenoid 
plug between pin A and ground 
(running) or between pin B and 
ground (cranking) 
Energize circuit (refer to Note 2 Page 7-2). Voltage 
should be approximately 12 VDC 
e. Check for continuity at the fuel 
solenoid plug between pin C and 
ground (running) 
f.  Check resistance of solenoid 
g. Check operation of solenoid 
Plunger must move in when energized 
a. Check fuel system prime. 
Unrestricted fuel flow through system. 
Check Engine Air-intake System 
b. Inspect air intake system. 
Hoses & tubes in good condition. 
No kinks or restrictions. 
Check For Correct Engine Oil 
a. Check for correct oil viscosity 
(weight) for conditions. 
Refer to Section 2.8.  
Must be correct for ambient conditions. 
Check Engine Exhaust System 
a. Inspect the exhaust system. 
Must be clear and unobstructed. 
a. Check engine compression.