EasyManuals Logo

Carrier VECTOR 1550 Series User Manual

Carrier VECTOR 1550 Series
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #151 background imageLoading...
Page #151 background image
62-61753-21
7-35
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
53 BOX TEMP OUT-OF-RANGE (Continued)
1
Check Refrigerated Compartment Doors
a. Inspect all box doors.
Must be closed, no air leakage.
2
Defrost Evaporator
a. Initiate Manual Defrost Cycle.
Must terminate automatically.
All ice cleared from all evaporator coils.
3
Check For Any Shutdown Alarm(s)
a. Check the Alarm List for any Shut-
down Alarms.
Alarm conditions must be corrected and the alarm
cleared to continue.
4
Check For Low Refrigerant Pressure Alarm
a. Check for alarm 18.
Alarm conditions must be corrected and the alarm
cleared to continue.
5
Check Refrigerant Charge
a. Check refrigerant level in the re-
ceiver.
Generally, level should be between upper & lower sight
glasses with a refrigerated compartment temperature
of 1.0°C (35°F) or lower. refer to Section 8.5.4
6
Check System Pressures
a. Install Manifold Test Set and check
and compare compressor dis-
charge & suction pressures with
those shown on the microproces-
sor.
Suction & Discharge Pressures must have the same
reading on gauges & on microprocessor display.
Pressures must be in the normal range for ambient &
refrigerated compartment temperature conditions.
NOTE: Microprocessor suction (CSP) and evapora-
tor (EVOP) pressure readings have a maximum
value of 7.5 bar (100 psig). The actual suction pres-
sure must be lower in order to perform this test.
7
Check Evaporator Section
a. Check evaporator section, return
air bulkhead, air chute, cleanliness
of evap. coil and airflow.
Refer to Section 9.4.10
8
Perform Pretrip Check
a. Clear Active Alarm list, then run
Pretrip & check for any new
alarms.
Any active alarms must be corrected and cleared be-
fore proceeding.
9
Check For Low Delta-T
a. Read Delta-T from Unit Data List.
In Cool, the Delta-T reading must be greater than -
0.56°C (-1°F).
Note for Delta-T readings a higher number after the "-"
sign is "greater than". For example, -3°C is greater
than -2°C.
In Heat the Delta-T must be greater than 0 (SAT must
be higher than RAT).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier VECTOR 1550 Series and is the answer not in the manual?

Carrier VECTOR 1550 Series Specifications

General IconGeneral
BrandCarrier
ModelVECTOR 1550 Series
CategoryRefrigerator
LanguageEnglish

Related product manuals