62-61753-21
7-39
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
59 DATALOGGER (DATACORDER) NOT RECORDING
TRIGGER-ON: No data is being recorded by the data recorder.
UNIT CONTROL: Engine and standby operation: alarm only.
RESET CONDITION: Alarm may be manually reset via keypad.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 Page 7-1) Operate the unit through the appropriate modes to see if any active alarm
occurs. Continue with the steps below as necessary.
1
Clear Alarm
a. Clear Active Alarm(s).
Alarms Clear.
b. Check for Active Alarm reoccur-
ring.
If Inactive, download all data & retain.
If Active, go to next step.
2
Microprocessor Defective
a. Replace microprocessor
Refer to Section 5.4