EasyManua.ls Logo

Carrier VECTOR 1550 Series - CONDENSER MOTOR OVERHEATED (Continued)

Carrier VECTOR 1550 Series
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62-61753-21
7-46
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
76 CONDENSER MOTOR OVERHEATED (Continued)
6
Check Condenser Fan Motors
a. Disconnect power plug at motor.
Test IP circuit for continuity using ohmmeter.
If open, remove and replace motor.
If closed, then an intermittent IP circuit is suspect.
Check phase to phase and phase to ground for short
or open circuits. Refer to Section 2.11.
If motor tests good, check the DC IP circuit to micro-
processor.
7
Check Motor Operation
a. Turn the unit ON.
Check current on each phase (must be less than
shown on Section 2.11.)
Check voltage on each phase (must be within voltage
limits shown in Section 2.11.)

Table of Contents

Related product manuals