P141 PRETRIP STOPPED BY USER
TRIGGER-ON: Pretrip cycle was stopped by user before the Pretrip cycle ended automatically.
UNIT CONTROL: Alarm Only.
RESET CONDITION: Alarm may be manually reset via keypad or by turning the unit off, then back on
again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 Page 7-1) Operate the unit through the appropriate modes to see if any active alarm oc-
curs. Continue with the steps below as necessary.
Check For Any Pretrip Alarms
a. Scroll the alarm list for any Active
Pretrip alarms.
Alarm conditions must be corrected and the alarm
cleared to continue.
Rerun Pretrip Check (If Desired)
a. Clear Active Alarm List, then run
Pretrip & check for any new
alarms.
Unit running in Pretrip. Check for any new alarms.
b. Allow to terminate automatically.
Pretrip cycle operates normally.
P145 CHECK SPEED SOLENOID CIRCUIT
TRIGGER-ON: Solenoid coil did not draw expected amperage during test
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again or alarm may be manually reset via key-
pad or by turning the unit off then back on again.
Check high speed operation - refer to alarm 38
P151 CHECK GLOW PLUG CIRCUIT
TRIGGER-ON: Glow plug circuit did not draw expected amperage during test
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again or alarm may be manually reset via key-
pad or by turning the unit off then back on again.
Check glow plug operation - refer to alarm 40
P152 CHECK FUEL SOLENOID CIRCUIT
TRIGGER-ON: Solenoid coil did not draw expected amperage during test
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again, or Alarm may be manually reset via key-
pad or by turning the unit off, then back on again.
Check fuel solenoid operation - refer to alarm 31 step 3
P153 CHECK RETURN AIR SENSOR
TRIGGER-ON: Sensor reading was not within the expected range during test.
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again, or alarm may be manually reset via key-
pad or by turning the unit off, then back on again.
Check Sensor - refer to alarm 122