62-61753-21
7-86
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
225 GENERAL MAINTENANCE DUE
TRIGGER-ON: The General Maintenance Hour Meter time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
a. Schedule unit into service facility
for maintenance.
Must be done soon!
2
Perform Maintenance
a. Perform appropriate engine & unit
maintenance.
Follow maintenance interval recommendations in
Section 8.2.
3
Reset General Maintenance Hour Meter
a. Reset hour meter for the next ser-
vice interval.
Reset Functional Parameter (refer to Table 3-2).
b. If hour meter interval is not set for
your requirements, reset the Con-
figuration, refer to Table 5-2.
Follow maintenance interval recommendations in
Section 8.2.
226 SERVICE SOON-PM #1 DUE
TRIGGER-ON: The Maintenance Hour Meter #1 time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
a. Schedule unit into service facility
for maintenance.
Must be done soon!
2
Perform Maintenance
a. Perform appropriate engine & unit
maintenance.
Follow instructions on proper maintenance form.
3
Reset Maintenance Hour Meter #1
a. Reset hour meter for the next ser-
vice interval.
Reset Functional Parameter (refer to Table 3-2).
b. If hour meter interval is not set for
your requirements, reset the Con-
figuration, refer to Table 5-2.
Follow maintenance interval recommendations in
Section 8.2.