62-61753-21   
242  DISCHARGE PRESS CALIBRATE ERROR 
  TRIGGER-ON: There is an error in the Compressor Discharge Pressure Sensor Calibration value 
stored in memory. 
  UNIT CONTROL: Alarm Only. 
  RESET CONDITION: See following instruction. 
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active 
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any 
active alarm occurs. Continue with the steps below as necessary. 
a. Place the Start/Run-Off switch in 
the OFF position for 30 seconds, 
then place it back in the RUN posi-
tion. 
Microprocessor powers up OK. 
b. Alarm 242 remains active. 
Replace microprocessor. Refer to Section 5.4 
243  SUCTION/EVAP CALIBRATE ERROR 
  TRIGGER-ON: There is an error in the Suction / Evaporator Pressure Sensor data processing. 
  UNIT CONTROL: Alarm only. 
  RESET CONDITION: See following instruction. 
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active 
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any 
active alarm occurs. Continue with the steps below as necessary. 
a. Place the Start/Run-Off switch in 
the OFF position for 30 seconds, 
then place it back in the RUN posi-
tion. 
Microprocessor powers up OK. 
b. Alarm 243 remains active. 
Replace microprocessor. Refer to Section 5.4