Test 8 - Evaporator Fan Motor Amperage 
Check 
The  evaporator  motor  contactor  is  energized  and 
check  for  proper  current  draw.  An  alarm  will  be  dis-
played if the fan motors test outside the current range 
(amps). 
Test 9 - Condenser Fan Motors Amperage 
Check 
The  condenser  motor  contactor  is  energized  and 
check  for  proper  current  draw.  An  alarm  will  be  dis-
played  if  fan  motors  test  outside  the  current  range 
(amps). 
Test 10 - Check Compressor Suction Modula-
tion Valve (CSMV) 
This test ensures that the CSMV is opening and clos-
ing  properly.  If  suction  pressure  doesn’t  change  as 
expected  with  CSMV  closed  then  "CHECK  SUCTION 
MOD  VALVE"  alarm  will  be  displayed  and  Pretrip  is 
aborted. This test may take several minutes. 
Test 11 - Electronic Expansion Valve (EVXV) 
This  test  checks  the  operation  of  the  EVXV.  If  valve 
doesn’t  test  properly  "CHECK  EVAP  SUPERHEAT" 
alarm will be displayed. 
NOTE 
Tests 12, 13 & 14 may be display only on Field 
Trial Units, depending on software revision. 
Test 12 - Unloader Solenoid Valve (USV) 
This test checks the operation of the unloader solenoid 
valve. If suction pressure does not change when USV 
is  de-energized,  the  "CHECK  BYPASS"  alarm  will  be 
displayed.  
Test 13 - Economizer Solenoid Valve (ESV) 
This test checks the operation of the economizer sole-
noid  valve.  If  discharge  pressure  does  not  change 
when ESV is energized, the "CHECK ECONOMIZER" 
alarm will be displayed.  
Test 14 - Liquid Injection Solenoid Valve (LIV) 
This  test  checks  the  operation  of  the  liquid  injection 
solenoid  valve.  If  compressor  suction  temperature 
does not change when LIV is energized, the "CHECK 
LIV" alarm will be displayed. 
Test 15 - Check For Other Alarms 
Checks the current alarm list for other active alarms. 
Pretrip Termination 
When  the  Pretrip  cycle  is  completed,  the  unit  will  
return  to  normal  temperature  control  operation.  
"PRETRIP  PASS"  will  be  displayed  in  the  Message-
Center until the operator presses any key. In the event 
that  the  Pretrip  test  triggered  an  alarm(s),  the  
MessageCenter  will  display  either  "PRETRIP  FAIL  & 
COMPLETE"  (if  the  entire  Pretrip  cycle  was  complet-
ed),  or  "PRETRIP  FAIL  IN  TEST  XX",  (if  the  Pretrip 
cycle was aborted by an alarm before it was complet-
ed).