NO METERS TO
RESET
OR
Expired Hour Meters
*If the PM Hourmeter is configured OFF, this parameter will not dis-
play
This Functional Parameter allows resetting of the PM Maintenance
Hour Meters when the hour meter has timed out, and preventative
maintenance has been performed.
Selecting RESET and pressing the "=" key will de-activate the alarm,
and reset the hour meter for the next service interval. The amount of
time added back into the meter before the next alarm trigger is deter-
mined by the PM Hour Meter Reset value entered in the meter Con-
figuration.
If the hour meter has been configured as active, this menu item will
not display.
If there are active maintenance hour meters and none have expired
and turned the alarm on, the MessageCenter will display
"NO METERS TO RESET."
*If the Door Switch is configured "Switch Not Installed", this parameter
will not display
NO - the microprocessor will respond to the door switch as configured
YES - the configured action on opening of the door will be overridden
and the action will be alarm only. The purpose of this setting is to
temporarily override the Configuration setting in situations where
shutdown or speed change is not desired.
*If the Remote Switch is configured "Switch Not Installed", this pa-
rameter will not display
NO - the microprocessor will respond to the remote switch as config-
ured
YES - the configured action for the switch will be overridden and the
action will be alarm only. The purpose of this setting is to temporarily
override the action in situations where shutdown is not desired.