137
T
Table 44: Pressure loss for design flow rates in LH installations (G8)
Nominal
pipe
size
Loss
of
pressure
in
pipe
Column
1
Column
2
(100
l/min)
Column
3
(225 l/min)
25
32
40
50
65
44,00
12
,00
5,50
1,70
0,44
198,00
52,00
25,00
7,80
2,00
G.2.4 Ordinary Hazard - OH
G.2.4.1
For
range
and
distribution
pipes,
the
dimensions
given
Table
G9
and
G10
shall
be
used.
Table 45: Range pipe diameters for OH installations (G9)
Range
pipes
Layout
Diameter mm
Maximum number
of sprinklers
fed
Ranges
at
remote
end of
all
distribution
pipes
2
end-side
layouts,
last
2
ranges
3
end-side
layouts,
last
3
ranges
All
other
layouts,
last
range
25
32
25
32
25
32
40
50
1
2
2
3
2
3
4
9
All
other
range
pipes
All
25
32
40
50
3
4
6
9