Table 46: Distribution pipe diameters in OH installations (G10)
Distribution
pipes
Layout
Diameter mm
Maximum number
of sprinklers
fed
At
extremities of
system
2
end-side
All
others
32
40
50
65
32
40
50
65
2
4
8
16
3
6
9
18
Between
design
points
and
the
control
valve
set
All
To
be
calculated
in
accordance
with
G.2.4.2
When
the
ranges
run
longitudinally
under
roofs
sloping
at
an
angle
of
more
than
6°,
the
number
of
sprinklers
on
a
range
pipe
shall
not
exceed
6.
The
use
of
65mm
diameter
pipe
between
the
design
points
and
the
control
valve
set
is
permitted
provided that
a
hydraulic
calculation
shows
this
to
be
possible.
NOTE:
figure
H4
gives
an
example
of
a
pipe
layout
in
OH
with
the
appropriate
design
points
from
which
the pipe
diameters
shall
be
fully
calculated.
G.2.4.2
The
pipe
diameters
between
the
design
point
in
the
most
remote
area
of
the
installation
and
the control
valve
set
shall
be
calculated
to
ensure
that
the
total
pressure
loss
due
to
friction
with
a
flow
of
1000l/min
does
not
exceed
0,5bar,
except
modified
in
G.2.4.3
and
G.2.4.4.
G.2.4.3
In
buildings
with
a
number
of
floors,
or
where
there
are
a
number
of
different
levels,
e.g.
:
platforms
or
lean-to’s,
the
0,5bar
loss
in
pressure
from
the
design
point
on
each
floor
may
be
increased
by
an
amount equivalent
to
t
he
static
pressure
due
to
the
height
difference
between
the
highest
level
and
the
floor concerned.
In
these
cases,
the
height
difference
between
the
highest
sprinkler
level
and
the
installation
pressure
gauge shall
be
indicated
on
the
completion
certificate,
together
with
the
pressure
required
at
the
installation pressure
gauge.
G.2.4.4
Where
the
same
system
includes
both
OH3
or
OH4
and
HHP
or
HHS
areas,
all
connected
to
a common
water
supply,
the
maximum
friction
loss
of
0,5bar
may
be
increased
by
50%
of
the
available
extra pressure,
as
indicated
in
the
following
example
for
OH3.
Example:
Pressure
required
at
the
control
valve
set
excluding
static
pressure
(Table
6
for
OH3)
1,4bar
Pressure
difference
due
to
the
difference
in
height
between
the
highest
sprinkler
and
the
control
valve
set
1,2bar
==============