139
Required
pressure
at
the
control
valve
set 2,6bar
Pressure
available
at
the
control
valve
set
for
the
flow
appropriate
in
HH
e.g. 6,0 bar
Extra
pressure
which
may
be
used:
50%
of
(6,0-2,6)= 1,7bar
The
pipework
shall
be
dimensioned
to
allow
for
a
maximum
pressure
loss
of:
0,5+1,7
(1
000/1
350)²
=
1,43bar
G.2.5 High hazard - HHP and HHS (except intermediate level sprinklers)
G.2.5.1
The
pipe
sizing
depends
upon:
-
the
design
density;
-
the
spacing
of
the
sprinklers;
-
the
K
factor
of
sprinkler
used;
-
the
pressure/flow
characteristic
of
water
supply.
No
pipe
shall
have
a
nominal
diameter
of
less
than
25mm.
G.2.5.2
For
installations
with
water
supplies
with
conform
to
the
demands
shown
in
Table
8
(1)
and
with sprinklers
having
a
K
factor
of
80,
the
pipe
sizes
for
range
pipes
and
distribution
pipes
shown
in
Tables
G11 and
G12
shall
apply.
No
more
than
4
sprinklers
shall
be
installed
on
any
range
pipe.
No
range
pipe
shall
be
connected
to
a distribution
pipe
exceeding
150mm
in
diameter.
100mm
diameter
pipe
may
be
installed
between
the
design points
and
the
control
valve
set
if
calculation
shows
this
to
be
possible.
NOTE:
figure
H5
gives
an
example
of
a
pipe
layout
in
accordance
with
Tables
G11
and
G12
and
design
points
from
which
the
pipe
diameters
shall
be
fully
calculated.
G.2.5.3
For
installations
with
water
supplies
which
conform
to
the
requirements
shown
in
Table
8
(2)
and with
sprinklers
having
a
K
factor
of
80,
the
pipe
sizes
for
range
pipes
and
distribution
pipes
shall
be determined
from
Tables
G11
and
G13.
No
more
than
4
sprinklers
shall
be
installed
on
any
range
Pipe.
No
range
pipe
shall
be
connected
to
a
distribution
pipe
exceeding
150mm
in
diameter.
No
distribution
pipe
less
than
65mm
diameter
is
permitted
for
4
end-side
systems.
150mm
diameter
pipe
may
be
installed
between
the
design
points
and
the
control valve
set
if
calculation
shows
this
to
be
possible.
NOTE:
figure
H6
gives
an
example
of
a
pipe
layout
in
accordance
with
Tables
G11
and
G13
and
design
points
from
which
the
pipe
diameters
shall
be
fully
calculated.
G.2.5.4
For
installations
with
water
supplies
which
conform
to
the
requirements
shown
in
Table
7
(3)
and with
sprinklers
having
a
K
factor
of
80,
and
as
shown
in
Table
8
(4)
with
sprinklers
having
a
K
factor
of
115,
the
pipe
sizes
for
range
pipes
and
distribution
pipes
shown
in
Tables
G13
and
G14
shall
apply.
In
an
end-side
arrangement,
no
more
than
6
sprinklers
shall
be
fitted
to
any
range
pipe.
In
a
two
end-
centre layout,
no
more
than
4
sprinklers
shall
be
fitted
to
any
range
pipe.
No
range
pipe
shall
be
connected
to
a distribution
pipe
exceeding
150mm
in
diameter.
No
distribution
pipe
less
than
65mm
diameter
shall
be
used
for
4
end-side
systems.
150mm
diameter
pipe
may
be
installed
between
the
design
points
and
the
control valve
set
if
calculation
shows
this
to
be
possible.

Table of Contents