140
NOTE:
figure
H7
gives
an
example
of
a
pipe
layout
in
accordance
with
Tables
G13
and
G14
and
design
points
from
which
the
pipe
diameters
shall
be
fully
calculated.
Table 47: Range pipe diameter for HH installations with pressure and flow characteristics
as given in Table 8
(1 or 2)(G11)
Range
pipes
Layout
Diameter
mm
Maximum
number
of
sprinklers
fed
by
pipe
Ranges
at
remote
end
of
all
distribution
pipes
2
end-side
layouts,
last
2
ranges
3
end-side
layouts,
last
3
ranges
All
other
layouts,
last
range
25
32
25
32
25
32
40
1
2
2
3
2
3
4
All
other
range
pipes
All
layouts
25
32
3
4
Table 48: Distribution pipe diameters downstream of the design point in HH installations with pressure and
flow characteristics as given in Table 8 (1) (G12)
Distribution
pipes
Diameter
mm
Maximum
number
of
sprinklers
fed
by distributio
n
pipe
Pipes
at
extremities
of
system
32
40
50
65
80
100
2
4
8
12
18
48
Pipes
between
the
design points
and
the
control
valve
set
To
be
calculated
in
accordance
with
G.2.5
Table 49: Distribution pipe diameters downstream of the design point in HH installations with pressure and flow
characteristics as given in Table 8 (2,3 or 4) (G13)
Distribution
pipes
Diameter
mm
Maximum
number
of
sprinklers
fed
by
distribution
pipe
Pipes
at
extremities
of
system
50
65
80
100
150
4
8
12
16
48
Pipes
between
the
design
points
and
the
control
valve
set
To
be
calculated
in
accordance
with
G.2.5