The
information
provided
shall
include
a
summary
schedule
(see
3.4.2),
complete
working
drawings
of
the
sprinkler
installation(s)
(see
3.4.3)
and
details
of
the
water
supplies
(see
3.4.4).
3.4.2 Summary schedule
The
summary
schedule
shall
give
the
following
information:
a)
the
name
of
project;
b)
all
drawing
or
document
reference
numbers;
c)
all
drawing
or
document
issue
numbers;
d)
all
dates
of
issue
of
drawings
or
documents;
e)
all
drawing
or
document
titles;
f)
the
type(s)
of
installation(s)
and
the
nominal
diameter(s)
of
each
control
valve
set;
g)
the
number
or
references
of
each
installation
main
control
valve
set
in
the
system;
h)
the
number
of
sprinklers
on
each
control
valve
set;
i)
the
piping
volume
in
the
case
of
dry
of
alternate
installations;
j)
the
height
of
the
highest
sprinkler
on
each
control
valve
set;
k)
a
statement
that
the
installation
will
comply
fully
with
these
rules
or
giving
details
of
any
deviations
from
their
requirements
and
the
reasons
therefore;
1)
a
list
of
approved
components,
included
in
the
system
each
identified
by
manufacturer's
name
and
model/reference
number.
3.4.3 Installation layout drawings
3.4.3.1 General
The
scale
shall
be
not
less
than
1:200.
Layout
drawings
shall
include
the
following
information:
a)
north
point
indication;
b)
the
class
or
classes
of
installation
according
to
hazard
class
including
storage
category
and
design
storage
height;
c)
constructional
details
of
floors,
ceilings,
roofs,
exterior
walls
and
walls
separating
sprinklered
and
non-sprinklered
areas;
d)
sectional
elevations
of
each
floor
of
each
building
showing
the
distance
of
sprinklers
from
ceilings,
structural
features,
etc.
which
affect
the
sprinkler
layout
or
the
water
distribution
from
the
sprinklers;