[DB600] General instruction manual
- 125 -
6-9-2
Transmission scale setting (PV /SV transmission)
For temperature input, set a value within the measuring range.
Input type ··················· K1(-200 to 1370°C)
Transmission signal ··· 4 to 20mA
Transmission scale ···· Zero: 400°C,
span: 1000°C
For linear input (mV, V), set a value within the linear scale range.
Input type ··················· 10V (-10V to 10V)
Transmission signal ··· 0 to 10V
Measuring range ········ Lower limit: 0V,
upper limit: 10V
Linear scale ················ Zero: -100.0,
span: 200.0
Transmission scale ···· Zero: 0, span: 100
6-9-3
Transmission scale setting (MV/MFB transmission)
For the case of outputting 30 to 70% of an output value as transmission signal of 4 to 20mA
Transmission signal ··· 4 to 20mA
Transmission scale ···· Zero: 30%, span: 70%
Transmission signal output with
transmission scale exceeding the range
of 0 to 100%
Relation with output limiter in MV
transmission
Calculation of output value is limited in the
range of -5 to 105%.
The output limiter is given higher priority.
Even if the transmission scale is set out of
the range of output limiter, output will be
limited by the output limiter range.