6-9-2
Transmission scale setting (PV /SV transmission)
For temperature input, set a value within the measuring range.
Input type ··················· K1(-200 to 1370°C)
Transmission signal ··· 4 to 20mA
Transmission scale ···· Zero: 400°C,
span: 1000°C
For linear input (mV, V), set a value within the linear scale range.
Input type ··················· 10V (-10V to 10V)
Transmission signal ··· 0 to 10V
Measuring range ········ Lower limit: 0V,
upper limit: 10V
Linear scale ················ Zero: -100.0,
span: 200.0
Transmission scale ···· Zero: 0, span: 100
6-9-3
Transmission scale setting (MV/MFB transmission)
For the case of outputting 30 to 70% of an output value as transmission signal of 4 to 20mA
Transmission signal ··· 4 to 20mA
Transmission scale ···· Zero: 30%, span: 70%
Reference
Transmission signal output with
transmission scale exceeding the range
of 0 to 100%
Relation with output limiter in MV
transmission
Calculation of output value is limited in the
range of -5 to 105%.
The output limiter is given higher priority.
Even if the transmission scale is set out of
the range of output limiter, output will be
limited by the output limiter range.
Transmission
signal output
Measuring
range
Transmission
scale range
(Zero)
(Span)
Transmission
signal output
Measuring range
Linear scale range
Transmission scale range
(Upper limit)
(Lower limit)
(Zero)
(Span)
Transmission
signal output
Transmission scale range
(Zero)
(Span)
Input type
Output value
Transmission
signal output
Transmission
signal output
Output range
Output range
(Zero)
(Span)
Transmission scale range
Output value
Transmission scale range
(Zero)
(Span)
(Upper limit)
(Lower limit)
Output value
Output limiter range

Table of Contents