[DB600] General instruction manual
- 138 -
9 Appendix
9-1 Specifications
Input specifications
B, R, S, N, K, E, J, T, U, L, WRe5-WRe26,
W-WRe26, Platinel II, PtRh40-PtRh20,
Au-Pt
Thermocouple 16 types, DC voltage 4
types, resistance thermometer 5 types
±0.1% of FS ±1digit of measuring range
See "◆ Input type, measuring range and
accuracy rating" for details.
Reference junction
compensation
accuracy
±1.0°C (ambient temperature 23°C ±10°C)
±2.0°C (temperatures other than above)
Upper limit burnout is provided for
thermocouple, resistance thermometer and
DC voltage (20mV) only as standard.
Output 1 produces PV abnormal output and
output 2 is fixed to 0% when burnout
occurs. Upper limit alarm event is output.
Thermocouple 1MOhm or more
DC voltage Approx. 1MOhm
Allowable signal
source resistance
Thermocouple 100Ohm or less
DC voltage (mV) 100Ohm or less
DC voltage (V) 300Ohm or less
Allowable wire
resistance
Resistance thermometer 10Ohm/1 wire or
less (resistance of 3 wires should be equal
to one another)
Resistance
thermometer
measurement current
Thermocouple ±10V DC
DC voltage (mV) ±10V DC
DC voltage (V) ±20V DC
Resistance thermometer ±5V DC
1500V
* This is a reference safety standard value
for UL/CSA61010-1, UL61010-2-030.
This value is not necessarily a guarantee
of instrument performance.
Maximum common
mode voltage
Common mode
rejection ratio
Series mode rejection
ratio
Display specifications
Segment type LCD
(LED backlight)
Control specifications
ON-OFF pulse output, ON-OFF servo
output (DB650 and DB670 only), current
output, SSR drive pulse output, voltage
output
ON-OFF pulse output type:
Resistive load 240V AC 3A
30V DC 3A
Inductive load 240V AC 1.5A
30V DC 1.5A
Minimum load 5V DC 10mA
ON-OFF servo output type:
Resistive load 240V AC 3A
30V DC 3A
Inductive load 240V AC 1.5A
30V DC 1.5A
Minimum load 5V DC 10mA
SSR drive pulse output type:
ON 12V DC ±20%
(load current 21mA or less)
OFF 0.8V DC or less
Specification with 2 outputs:
Any combination between ON-OFF pulse,
output, current output, SSR drive pulse
output and voltage output is possible.
Non-isolated between 2 outputs (ON-OFF
pulse output type excluded)
Event function
Absolute value alarm, deviation alarm,
absolute value deviation alarm, set point
alarm, output value alarm, heater
disconnection alarm (only for the case
adjustment output 1 uses ON-OFF pulse
output or SSR drive pulse output), timer 1,
timer 2, FAIL
Constant value operation RUN, preset
manual, remote input, SV rise, SV fall
Program function:
Step switching, step 1 to 12, RUN, STOP,
ADVANCE, RESET, END, SV keep