[DB600] General instruction manual
- 139 -
General specifications
Rated power voltage 100-240V AC(±10%)
24V AC
/
DC(±10%)
Rated power supply frequency 50
/
60Hz(±2%)
Maximum power consumption:
100 to 240V AC (without option)
DB630 100V AC 4VA
240V AC 5VA
DB650 100V AC 4VA
240V AC 6VA
DB670 100V AC 4VA
240V AC 6VA
100 to 240V AC (with option)
DB630 100V AC 5VA
240V AC 7VA
DB650 100V AC 7VA
240V AC 10VA
DB670 100V AC 9VA
240V AC 12VA
24V AC/DC (without option)
DB630 24V AC 3VA
24V DC 2W
DB650 24V AC 4VA
24V DC 3W
DB670 24V AC 4VA
24V DC 3W
24V AC/DC (with option)
DB630 24V AC 4VA
24V DC 3W
DB650 24V AC 7VA
24V DC 5W
DB670 24V AC 8VA
24V DC 6W
Countermeasure
against power
failure
Store setting contents in non-volatile memory.
(Rewrite: 1 million times)
Between the primary and secondary terminals
20MOhm or more (500V DC)
* Primary terminal: Power terminal
(100 to 240V AC),
EV1 to 4 output
terminals (relay output),
ON-OFF pulse output
terminal (relay output),
ON-OFF servo output
terminal (M3, M2, M1)
Secondary terminal: Power terminal
(24V AC/DC),
all terminals except
primary terminals
Between the primary and secondary terminals
1500V AC (1 minute)
* See "Insulation resistance" for the primary
and secondary terminals.
Front: Fire-retardant acrylonitrile butadiene
styrene/polycarbonate (UL94V-0)
Case: Fire-retardant polycarbonate (UL94V-2)
DB630 48(W)×48(H)×88(D)
(Depth from panel surface is 80)
DB650 48(W)×96(H)×73(D)
(Depth from panel surface is 65)
DB670 96(W)×96(H)×73(D)
(Depth from panel surface is 65)
DB630 (Without option) Approx. 120g
(With option) Approx. 135g
DB650 (Without option) Approx. 150g
(With option) Approx. 230g
DB670 (Without option) Approx. 240g
(With option) Approx. 330g
DB630 At the bottom of the case
DB650 At the top of the case
DB670 At the top of the case
Reference operating condition
55%RH±5% (no condensation)
Backward/forward ±3°, laterally ±3°
Single panel mounting (space required
around)
Normal operating condition
-10 to 50°C
(-10 to 40°C for close installation)
Maximum ambient humidity (ambient temperature -10 to 31°C)
Maximum ambient humidity (ambient temperature 31 to 50°C)
90 to 50% RH (no condensation)
* Decreases linearly from 90% RH at 31°C, or to 50% RH at 50°C.
Backward/forward ±10°, laterally ±10°
Panel mounting (space above and below)
Ambient temperature
variation ratio
Transport condition
5 to 95% RH (no condensation)
4.9m/s
2
or less (10 to 60Hz)
392m/s
2
or less (under factory packing
condition)