3. Select the Control tab.
4. Select the RH Influence On Minimum Ventilation
box if you want the min/vent timer to be influenced
by the RH.
5. The Minimum Ventilation timer will be adjusted
based on house RH when the temperature is between
set temperature and the Min-Vent fan's ON tempera-
ture. The Control will adjust the amount of ON time
between the Min Ventilation value and the Max val-
ue. The OFF time will be adjusted by the same
amount of time that the ON is adjusted, thus keeping
the total cycle time constant. The temperature is
checked 30 seconds before the beginning of the ON time cycle of the Mini-
mum Ventilation Timer. This is in addition to any time added by Ventilation
Timer Ramping.
6. Amount Of Influence (sec)- is the amount of decrease or increase time pre movement.
7. Maximum Influence(sec)- is the maximum amount of RH timer influence you need.
Once the fans' temperature sensor(s) reach the fans' ON temperature, the
fan will turn on and run continuously until the fans' OFF temperature is
reached.
Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run con-
tinuously until the fans' OFF temperature is reached.