InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
112
% (hence the desired values are reached).
12.2.2.7 Setpoint: BusRNomV
Group
Basic Settings
Range [units]
10 .. 30000 [V]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used to adjust the nominal busR voltage (phase to neutral). If
you do not know the phase-neutral nominal voltage, you can adjust the
phase-phase nominal voltage busRNomVph-ph. The controller will then
recalculate the phase-neutral nominal voltage automatically.
NOTE:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
NOTE:
If different voltage on BusL and on BusR is required the following procedure
is required:
Both setpoints (BusRNomV and BusLNomV) must be adjusted to the same
values according to the value of actual BusL or BusR nominal voltage. E.g.
BusR nominal is 231 V but BusL nominal is 240 V.
In this case both setpoints need to be adjusted to 231 V and setpoints of
corresponding protections for BusL need to be set assymetrically.
For 240 V on BusL it is typical to open BTB when voltage reaches 254 V or
225 V. Since the setpoint is adjusted to 231 V corresponding protection
setpoints need to be adjusted to BusRight >V = 106% and BusRight <V = 97
% (hence the desired values are reached).
12.2.2.8 Setpoint: BusRNomVph-ph
Group
Basic settings
Range [units]
17 .. 60000 [V]
Related FW
3.0
Description
This setpoint is used to adjust the nominal busR voltage (phase to phase).
This setpoint is also recalculated automatically when the phase-neutral
nominal voltage busRNomV is changed.
This setpoint can be used if you know the phase-phase nominal voltage only.
The controller will recalculate the phase-neutral nominal voltage

Table of Contents