InteliLite4 AMF20 Global Guide
287
Subgroup:Dummy Load
Dummy Load Active
Setpoint group Load Management Related FW 1.3.0
Range [units] GenOnly / Disable [-]
Default value Disabled Alternative config YES
Step [-]
Comm object 11776 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables / disables Dummy Load function.
IMPORTANT: If Gen Only option is chosen, no dummy load will be activated when in
parallel with mains.
6 back to List of setpoints
Dummy Load On
Setpoint group Load Management Related FW 1.3.0
Range [units] 0.0 .. Dummy Load Off (page 288) [%]
Default value 20 % Alternative config YES
Step 0.1%
Comm object 11772 Related applications AMF,MRS
Config level Advanced
Setpoint visibility If Dummy Load Active (page 287) is not set to disabled
Description
This setpoint determines power level which when not matched will trigger Dummy Load Function to
activate additional power bank level (by activating additional Dummy Load Stage LBOs).
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals