InteliLite4 AMF20 Global Guide
286
Load Reconnection Delay
Setpoint group Load Management Related FW 1.3.0
Range [units] 0 .. 600 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 8893 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Visible only if Load Shedding Active (page 284) is enabled
Description
This setpoint is used to proceeds the lower Load shedding stage. When Gen-set load drops under Load
Reconnection Level (page 285) for more than this delay time, the binary output for higher stage is
opened. Automatic load reconnection works only when Auto Load Reconnection (page 286) = Enabled
6 back to List of setpoints
Auto Load Reconnection
Setpoint group Load Management Related FW 1.3.0
Range [units] Disabled / Enabled [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 9649 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Visible only if Load Shedding Active (page 284) is enabled
Description
Switch between manual and automatic reconnection of shedded load..
Disabled
Rising edge on binary input MANUAL LOAD RECONNECTION (PAGE 452) resets
controller to the lower stage, but only if the load is under the Load Reconnection
Level (page 285). Load Reconnection Delay (page 286) is not taken into account in
this case.
Enabled
Load reconnection is automatic depend on setpoints Load Reconnection Level
(page 285) and Load Reconnection Delay (page 286). Binary input MANUAL LOAD
RECONNECTION (PAGE 452) has no function.
6 back to List of setpoints