InteliLite4 AMF20 Global Guide
541
Generator <> Voltage Delay (page 266)
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Generator L2L3 > Voltage
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 2
and 3. The following setpoints are related to it:
Generator Overvoltage Wrn (page 264)
Generator <> Voltage Delay (page 266)
Wrn Generator L2L3 Overvoltage
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Generator L3L1 > Voltage
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 3
and 1. The following setpoints are related to it:
Generator Overvoltage Wrn (page 264)
Generator <> Voltage Delay (page 266)
Wrn Generator L3L1 Overvoltage
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Generator L1 < Voltage
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator phase voltage in phase 1. The following
setpoints are related to it:
Generator Undervoltage Wrn (page 265)
Generator <> Voltage Delay (page 266)
Wrn Generator L1 Undervoltage
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Generator L2 < Voltage
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator phase voltage in phase 2. The following
setpoints are related to it:
Wrn Generator L2 Undervoltage