InteliLite4 AMF20 Global Guide
574
Related applications AMF,MRS
Description
The alarm is active when the value Maintenance Timer 2 RunHours (page
413) reaches 0.
The value is adjustable by setpoint Maintenance Timer 2 RunHours (page
257) (unit is hours-h) and it counts down while engine is running. Setpoint
Maintenance Timer 2 Protection (page 258) has to be set to: BOC
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Maintenance Timer 2 Interval
Alarm evaluated All the time
Related applications AMF,MRS
Description
The alarm is active when the value Maintenance Timer 2 RunHours (page
413) reaches 0.
The value is adjustable by setpoint Maintenance Timer 2 Interval (page 258)
(unit is in months-m) and it counts down in days based on actual date (No matter
if engine is running or not). Setpoint Maintenance Timer 2 Protection (page
258) has to be set to: Warning
BOC Maintenance Timer 2 Interval
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Maintenance Timer 3 RunHours
Alarm evaluated All the time
Related applications AMF,MRS
Description
The alarm is active when the value Maintenance Timer 3 RunHours (page
413) reaches 0.
The value is adjustable by setpoint Maintenance Timer 3 RunHours (page
259) (unit is hours-h) and it counts down while engine is running. Setpoint
Maintenance Timer 3 Protection (page 260) has to be set to: BOC
BOC Maintenance Timer 3 RunHours
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Maintenance Timer 3 Interval
Alarm evaluated All the time
Related applications AMF,MRS
Description
The alarm is active when the value Maintenance Timer 3 RunHours (page
413) reaches 0.
The value is adjustable by setpoint Maintenance Timer 3 Interval (page 259)
(unit is in months-m) and it counts down in days based on actual date (No matter
if engine is running or not). Setpoint Maintenance Timer 3 Protection (page
260) has to be set to: Warning
BOC Maintenance Timer 3 Interval

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals