InteliLite4 AMF20 Global Guide
576
Related applications AMF,MRS
Description
This alarm evaluates the GPSposition of Gen-set. The following setpoint are
related to it:
Geo-Fencing (page 324)
Fence 1 Protection (page 326)
Fence 1 Radius (page 327)
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Parallel Work
Alarm evaluated All the time
Related applications AMF,MRS
Description This alarm is active when GCB is closed externally while MCB is closed.
Sd Parallel Work
6 back to List of alarms level 2
8.3 Modules
8.3.1 Plug-in modules
The available communication plug-in modules are:
CM-RS232-485 communication module for connection via RS232 or RS485 line
CM2-4G-GPS communication module for connection via 4G
CM3-Ethernet communication module for internet connection via Ethernet
The available extension plug-in modules are:
EM-BIO8-EFCP extension module with 8 binary inputs/outputs and with earth fault current protection
Note: Controller has 2 plug-in module slots.
Module CM3-Ethernet CM2-4G-GPS CM-RS232-485 EM-BIO8-EFCP
CM3-Ethernet
CM2-4G-GPS
CM-RS232-485
EM-BIO8-EFCP
Supported combinations of plug-in modules
Communication modules
CM-RS232-485 577

Table of Contents

Related product manuals