Group: Geo-Fencing
Subgroup:Geo Fencing
Geo-Fencing
Setpoint group Geo-Fencing Related FW 1.3.0
Range [units] Disabled / Enabled / LBI Enable [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 11681 Related applications AMF,MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables geo-fencing function.
Disabled
Fence 1 Protection (page 326) and Fence 2 Protection (page 328) are
disabled.
Enabled
Fence 1 Protection (page 326) and Fence 2 Protection (page 328) are
enabled.
LBI Enable
Fence 1 Protection (page 326) and Fence 2 Protection (page 328) are
enabled only when logical binary input .GEO-FENCING ENABLE (PAGE 451) is
active.
6 back to List of setpoints
Subgroup:Position
Home Latitude
Setpoint group Geo-Fencing Related FW 1.3.0
Range [units] -90,0000..90,0000 [°]
Default value 0,0000 ° Alternative config NO
Step 0,0001 °
Comm object 14606 Related applications AMF,MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjust latitude of "home" position. Home is position where gen-set should runs. Positions on
north hemisphere have positive value, position on south hemisphere have negative value.
Note: This value with Home Longitude (page 325) are used for counting Fence 1 Radius (page
327) and Fence 2 Radius (page 329).
Note: This value can be also obtained automatically via logical binary input GEO HOME POSITION
(PAGE 450). In case of activation of this binary input for at least 2 seconds, setpoint will be adjusted
automatically from actual coordinates from GPS signal.
6 back to List of setpoints