EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #451 background imageLoading...
Page #451 background image
InteliLite4 AMF20 Global Guide
451
Related FW 1.3.0 Related applications AMF,MRS
Comm object 218
Description
This binary input enables or disables Fence 1 Protection (page 326) and Fence 2 Protection (page
328) if Group: Geo-Fencing (page 324) is adjusted to value "LBI Enable".
Geo-Fencing Enable
6 back to Logical binary inputs alphabetically
LBI: H
Related FW 1.3.0 Related applications AMF,MRS
Comm object 192
Description
Binary input has the same function as Horn reset button on the InteliLite 4 front panel.
Horn Reset Button
6 back to Logical binary inputs alphabetically
LBI: I
Related FW 1.3.0 Related applications AMF,MRS
Comm object 624
Description
This binary input changes cooling speed from nominal to idle.
Idle Speed
6 back to Logical binary inputs alphabetically
LBI: M
Related FW 1.3.0 Related applications AMF,MRS
Comm object 622
Description
If the input is active, the automatic start of the Gen-set at Mains failure is blocked. In case of running Gen-
set in AUTO mode, timer Mains Return Delay (page 269) is started and when it elapses GCB is opened,
Gen-set goes to cooling procedure and stops. When GCB is opened after Transfer Delay (page 270) the
MCB is closed.
Note: This input simulates healthy Mains.
Mains Fail Block
6 back to Logical binary inputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals