InteliLite Global Guide
240
Setpoint group Dual Operation Related FW 1.9.0
Range [units] -10 000,0 .. 10 000,0 [h]
Default value 0 h Alternative config NO
Step 0,1 h
Comm object 16040 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
343) and COM2 Mode (page 345)
Description
This setpoint modifies the running hours of controller used in dual operation function. Negative value is
decrement from running hours, positive value is increment to running hours.
Example:
Master controller has 1000 h.
Slave controller has 100 h.
Adjust setpoint of slave controller to 900 h to have both controllers on "0" running hours in dual
operation.
Running Hours Base
6 back to List of setpoints
Setpoint group Dual Operation Related FW 1.9.0
Range [units] Enabled / Disabled [-]
Default value Enabled h Alternative config NO
Step [-]
Comm object 16041 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
343) and COM2 Mode (page 345)
Description
This setpoint enables or disables swapping of gen-sets on load in dual operation.
Enabled Master and Slave are swapped based on their actual running hours.
Disabled
Master and Slave are not swapped. Controller with lower running hours starts and then runs
until mains returns or until controller shutdown - then second controller starts.
Swap Gen-sets
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals