InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008 19
IL-NT-AMF-Reference Guide1.2.pdf
Or by connecting special I-LBA module:
Hint
:
I-LBA may not eliminate voltage drop when used with low temperature (-40°C) version of controller
and display heating element is on (below 5°C). Current drain of heating element exhausts LBA
capacitors very fast .
Power supply fusing
A one-amp fuse should be connected in-line with the battery positive terminal to the controller and
modules. These items should never be connected directly to the starting battery.
Fuse value and type depends on number of connected devices and wire length.
Recommended fuse (not fast) type - T1A. Not fast due to internal capacitors charging during
power up.