IL-NT-AMF-Reference Guide1.2.pdf
Binary output protections
Hint
Do not connect binary outputs directly to DC relays without protection diodes, even if they are not
connected directly to controller outputs.
Grounding
To ensure proper function:
Use as short as possible cable to the grounding point on the switchboard
Use cable min. 2,5mm
2
The “-“ terminal of the battery has to be properly grounded