InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008 34
IL-NT-AMF-Reference Guide1.2.pdf
GCB Off Coil
The output deactivates Generator Circuit Breaker coil.
GCB UV Coil
The output controls Generator Circuit Breaker coil after voltage drop-out.
MCB Close/Open
The output controls the mains circuit breaker.
MCB On Coil
The output activates Mains Circuit Breaker coil.
MCB Off Coil
The output deactivates Mains Circuit Breaker coil.
MCB UV Coil
The output controls Mains Circuit Breaker coil after voltage drop-out.
Gen Healthy
The output is a copy of generator status LED on IL-NT front panel. The output is closed if gen-set is
running and all gen-set electric values are in limits.
Ready To AMF
The output is active, if the controller is able to start the engine (the output Ready is active) or engine is
already running and simultaneously the controller is in AUT Mode.
Ready
The output is closed if following conditions are fulfilled:
Gen-set is not running and
No Shutdown protection is active
Controller is not in OFF Mode
Ready To Load
The output is closed if gen-set is running and all electric values are in limits and no alarm is active - it
is possible to close GCB or it is already closed. The output opens during cooling state.
Mains Healthy
The output is copy of mains status LED on IL-NT front panel. The output is closed if mains voltage and
frequency are within limits.
AL Gen >V
The output closes if the generator overvoltage shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen <V
The output closes if the generator undervoltage shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen Volts
The output closes if the generator over/under voltage alarm or voltage asymmetry alarm activates.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite NT AMF Series and is the answer not in the manual?

ComAp InteliLite NT AMF Series Specifications

General IconGeneral
BrandComAp
ModelInteliLite NT AMF Series
CategoryController
LanguageEnglish

Related product manuals