InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008 37
IL-NT-AMF-Reference Guide1.2.pdf
AL AI3 Sd
Output closes if the Fuel level (configured to the third analog input) shutdown alarm activates.
AL AI3 Wrn
Output closes if the Fuel level (configured to the third analog input) warning alarm activates.
Running
Output closes if the engine is in Running state.
AL Common Wrn
Output closes when any warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
AL Common Sd
Output closes when any shut-down alarm appears.
The output opens, if
No sd alarm is active and
FAULT RESET is pressed
AL Common Fls
Output closes when any sensor fail alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Mode OFF
The output is closed, if OFF Mode is selected.
Mode MAN
The output is closed, if MAN Mode is selected.
Mode AUT
The output is closed, if AUT Mode is selected.
Mode TEST
The output is closed, if TEST mode is selected.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
AL D+ Fail
Output closes if gen-set is running and D+ input not energized.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Hint:
Treshhold level for D+ input is 80% supply voltage.
Maintenance
Output closes if the Maintenance alarm activates, i.e. the gen-set has been running for more than
Engine Protect:Maintenance.
The output opens, if