InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008      36 
IL-NT-AMF-Reference Guide1.2.pdf 
AL Underspeed 
Output closes if the gen-set underspeed alarm activates.  
The output opens, if 
•  alarm is not active and 
•  FAULT RESET is pressed  
AL Start Fail 
Output closes after the gen-set start-up fails.  
The output opens, if 
•  alarm is not active and 
•  FAULT RESET is pressed  
AL Overcurrent 
Output closes if the generator  
*IDMT over current or  
current unbalance or  
short current alarm activates.  
The output opens, if 
Alarm is not active and 
FAULT RESET is pressed  
AL BatteryFlat 
Output closes when IL-NT performs reset during start procedure (probably due to weak battery) or 
when battery under voltage warning appears. 
The output opens, if 
•  alarm is not active and 
•  FAULT RESET is pressed 
AL AI1 Sd 
Output closes if the oil pressure (configured to the first analog input) shutdown alarm activates. 
The output opens, if 
•  alarm is not active and 
•  FAULT RESET is pressed 
AL AI1 Wrn 
Output closes if the oil pressure (configured to the first analog input) warning alarm activates. 
The output opens, if 
•  alarm is not active and 
•  FAULT RESET is pressed 
AL AI2 Sd 
Output closes if the water temperature (configured to the second analog input) shutdown alarm 
activates. 
The output opens, if 
•  alarm is not active and 
•  FAULT RESET is pressed 
AL AI2 Wrn 
Output closes if the water temperature (configured to the second analog input) warning alarm 
activates. 
The output opens, if 
•  alarm is not active and 
•  FAULT RESET is pressed