This setpoint is used for adjusting the maximal allowed power imported from
the mains. It is used as the 100% for the IDMT overload protection
(Mns2PovrldProt) as well as for some regulation loops.
NOTE:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
11.2.2.11 Setpoint: MainsCTprim
Nominal current of the primary side of the mains current transformers. The
secondary side is adjusted by setpoint MainsCTsec.
11.2.2.12 Setpoint: MainsCTsec
Nominal current of the secondary side of the mains current transformers.
The primary side is adjusted by setpoint MainsCTprim.
NOTE:
The CT secondary nominal current is adjustable only in IM-NTC. The IM-NT
has the CT secondary nominal current adjusted fixedly to 5A regardless of
this setpoint.
11.2.2.13 Setpoint: AuxCurrCTprim