InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
188
NOTE:
In the case that more IV displays are connected they all behave the same (they
are all clones of each other).
NOTE:
The binary inputs for external buttonst may be the following (depending on used
application): GCBButton, MCBButton, MGCBButton, FDRButton, BTBButton,
FaultResButton, HornResButton, StartButton, StopButton etc.
11.2.2.20 Setpoint: DispBaklightTO
Group
Basic settings
Range [units]
OFF, 1-240 min, NO TIMEOUT [min]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts timeout after which the display (internal display or IS
display #1) backlight is switched off.
NOTE:
When IntelliVision is used this setpoint does not adjust its behavior. Its
backlight is adjusted by internal IntelliVision "setpoint".