11.2.3.4 Setpoint: RS232(1) mode
DIRECT, MODEM (HW), MODEM (SW), MODBUS-DIRECT, MODBUS-
MDM(HW), ECU LINK [-]
This setpoint selects the connection type for the serial port COM1.
Available as RS232 in all controller types.
Available also as RS485 in the IG-NT if the external display bus is
not used. Selectable by the setpoint RS485(1) conv. (not available in
IG-NT-BB, IG-NTC-BB, IS-NTC-BB and IS-NT - see RS485(1)
conv.).
See the diagram of all related terminals in the chapter Communication.
Connection to a local PC via RS232 or RS485
(with internal or external converter) interface.
Use this option also for IG-IB connected via
RS232 cable. The internal RS485 converter is
enabled/disabled by the setpoint RS485(1)
conv.
Modem point-to-point connection to a remote
PC with hardware data flow control using
signals RTS/CTS. Full modem cable is required
for this option.
Modem point-to-point connection to a remote
PC with software data flow control. 3-wire cable
(RX, TX, GND) is sufficient for this option. Use
this option only if your modem does not provide
RTS/CTS signals.
Modbus RTU connection in slave mode via
RS232 or RS485 (with internal or external
converter) interface. The internal RS485
converter is enabled/disabled by the setpoint
RS485(1) conv., the communication speed is
adjustable by the setpoint RS232(1)MBCSpd.
See the latest communication guide for more
information about MODBUS protocol.
Modbus RTU connection in slave mode via
modem with hardware data flow control. The
communication speed is adjustable by the
setpoint RS232(1)MBCSpd. See the latest