InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
201
FIXED
The ethernet connection is adjusted fixedly according to
the setpoints IP address, Net mask, Gateway IP, DNS
IP. .
This method should be used for classic ethernet or
Internet connection. When this type of connection is
opening the controller is specified by it's IP address.
That means it would be inconvenient if the IP address
were not fixed (static).
AUTOMATIC
The ethernet connection settings is obtained
automatically from the DHCP server. The obtained
settings is then copied to the related setpoints (it is not
possible to set those setpoints manually in this setting,
for more information please see the following setpoints:
IP address, Net mask, Gateway IP and DNS IP). If the
process of obtaining the settings from DHCP server is
not successful the value 000.000.000.000 is copied to
the setpoint IP address and the module continues trying
to obtain the settings.
This method is beneficial for AirGate connection as it
makes the connection very easy, in fact "plug and play".
When this type of connection is opening the controller is
specified by it's AirGate ID and the IP address does not
play any role.
CAUTION!
If you need to use fixed ethernet settings you should consult the proper
setting with your IT specialist.
11.2.3.19 Setpoint: IP address
Group
Comms settings
Range [units]
[-]
Related FW
standard v3.1.0
Description
In fixed settings mode this setpoint is used to adjust the IP address of
the ethernet interface of the controller. Ask your IT specialist for help
with this setting.
In Automatic settings mode this setpoint is used to display the IP
address, which has been assigned by the DHCP server. It is not
possible to change the setpoint value manually in this setting (the
value is immediately reverted back by controller communication
module IB-COM).