EasyManua.ls Logo

ComAp InteliMains NT IM-NT-BB - Page 237

ComAp InteliMains NT IM-NT-BB
437 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
237
used in some situations to allow genset start after Sys Start/Stop gets active.
It is not destined for normal operation. Please refer to the Troubleshooting
guide for more information (chapter "MGCB is not closed although gensets
are running").
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.13 Setpoint: #LoadResStop 4
Group
Pwr Management
Range [units]
LoadResStrt 4 .. 32000 [kX]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
Pwr mgmt mode = ABS (kW) or ABS (kVA) if the reserve set #4 is active.
Learn more about reserves in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load
res 3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for
start.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.14 Setpoint: #%LdResStrt 1
Group
Pwr Management
Range [units]
0 .. %LdResStop 1 [%]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the load reserve for start in relative mode. i.e.
Pwr mgmt mode = REL (%) if the reserve set #1 is active. Learn more about
reserves in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load
res 3 and Load res 4. If none of these inputs is active the set #1 is selected.

Table of Contents