# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.25 Setpoint: #SlowStopDel
This setpoint is used to adjust how long the particular gen-set will suppress
it's own Slow stop alarm to give chance to another gen-set to start and
replace the defective one.
If there isn't any available gen-set to start, the alarm is not suppressed.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.26 Setpoint: #MinRunPower 1
This setpoint is used to adjust certain minimum value of the sum of nominal
power of all running gen-sets. If the function is active, then the gen-sets
would not be stopped, although the reserve for stop is fulfiled, if the total
remaining nominal power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated
by the input MinRun power 1 which is in MINT application (in InteliMains it is
for compatibility purposes only).
NOTE:
When more than one binary input MinRunPower is activated then
MinRunPower with the highest number is active.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.