InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.34 Setpoint: #PwrBnChngDlUp
This setpoint is used for adjusting the delay of changing the power band if the
load demand rose above the upper limit of the current power band. Learn
more about this topis in the chapter Gen-set size optimalization.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.35 Setpoint: GroupLinkLeft
NOTE:
In MCB/MGCB application both GroupLinkLeft and GroupLinkRight should be
set to 1 (=COMMON).
If the input GroupLink of this particular controller is used to provide the "group
link" information for two logical groups, then this setpoint is used to select
which group is located at the left side of the group link breaker (bus tie
breaker). If this particular controller is not used for the group link function
adjust this setpoint to 1 (COMMON).
11.2.9.36 Setpoint: GroupLinkRight