InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
11.2.10.4 Setpoint: Dwell time
This setpoint adjusts the period of time that the phase angle difference must
stay within +/-Phase Window and voltage difference within Voltage Window
before the respective breaker, which is actually beeing synchronized, is
closed.
11.2.10.5 Setpoint: Freq gain
This setpoint adjusts the gain factor (P-factor) of the frequency control PI
loop. The integration factor (I-factor) for the frequency loop is adjusted by the
setpoint Freq int.
FREQ GAIN AND FREQ INT SETPOINTS ARE ACTIVE DURING:
reverse synchronization of the gen-set group back to the
mains